Carrier 41 Blower Motor Fault. Carrier 1/3 HP Gas Furnace Blower Motor HB41TQ113 Shortys HVAC Supplies Just a quick video showing how I was able to quickly troubleshoot and fix a blower motor fault 41 on a Carrier Infinity AC unit.Feel free to use the affiliat. The motor appears to be fine with ohm readings as follows: I Set ohm meter to lowest possible setting and
Carrier Furnace Fault Code 41—What Is Wrong? from hvacseer.com
All other functions appear to be operating normally, AC condensing unit runs as. Just a quick video showing how I was able to quickly troubleshoot and fix a blower motor fault 41 on a Carrier Infinity AC unit.Feel free to use the affiliat.
Carrier Furnace Fault Code 41—What Is Wrong?
Replace entire blower motor including blower control module All other functions appear to be operating normally, AC condensing unit runs as. The good news is that Carrier furnace fault code 41 has straightforward solutions
Carrier Furnace Fault Code 41—What Is Wrong?. I don't know if it is the main control board or the module on the motor. · Blower motor speed is less than 250 RPM or greater than 1300 RPM for more than 10 sec.
[DIAGRAM] Carrier Air Conditioner Blower Motor Wire Diagram MYDIAGRAM. Carrier provided troubleshooting steps identified the motor module as the source of the problem If STATUS LED is indicating Status Code 41, motor control has detected that the motor will not come up to speed within 30 seconds of being commanded to run or that the motor has been slowed to below 250 rpm for more than 10 seconds after coming up to speed.